Weil-McLain Error Code CONFIGURATION: Control board not configured (Boiler)

Updated · by Aurora Star Tech Inc.

Weil-McLain error code CONFIGURATION on a boiler means: Control board not configured. It is also called Weil-McLain diagnostic code CONFIGURATION.

High severityBoilerWeil-McLain CGa Series 4

Homeowner? What Weil-McLain code CONFIGURATION means for you

Call a technician Your boiler is reporting: Control board not configured. The boiler has locked out or cannot run properly. One reset is fine; if the code comes back, it needs a licensed technician to find the cause.

Safe things you can check yourself

  • Check the thermostat: right mode (Heat or Cool), set a few degrees past room temperature, and fresh batteries if it uses them.
  • Make sure the unit has power: its on/off switch (often looks like a light switch near the unit) is ON and the breaker in the electrical panel is not tripped.
  • Look at the pressure gauge on the boiler. If it reads much lower than usual or near zero, or water is leaking, call a technician.
  • Outside, make sure the intake and exhaust pipes or vent cap are not blocked by snow, ice, leaves or a nest.
  • Check that the boiler gas valve is open (handle in line with the pipe).
  • Try one reset: turn the power off for 30 seconds, then back on. If the code comes back, stop resetting and call a technician.

Call (647) 657-2977Book a service call

Licensed technicians serving Vaughan, Toronto and the GTA.

What does Weil-McLain error code CONFIGURATION mean?

The control has not been set up for this boiler yet. The display is red and the boiler will not fire until the configuration is confirmed.

Applies to: CGa-25 to CGa-8, natural gas (config #15) and propane (config #5)

Common causes of Weil-McLain code CONFIGURATION

  • New or replacement control that has never been configured
  • Missing 24 VAC on the model-setting pins of P13 (harness problem)
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

Other Weil-McLain Boiler codes

CodeMeaning
BOILER OUT OPENBoiler outlet sensor open circuit
BOILER OUT SHORTBoiler outlet sensor shorted
BURNER ONBurner on status
CHCentral heat call active
CH VOLTAGE HIGHToo much voltage on the CH / Thermostat 1 input
CONFIG MISMATCHStored configuration does not match the harness
DHWDomestic hot water call active
DHW VOLTAGE HIGHToo much voltage on the DHW / Thermostat 2 input
DISPLAY COMMDisplay communication lost
EXP BOARD COM FAULTExpansion board to U-Control communication fault
FALSE FLAMEFlame sensed when the gas valve is off
FAULT L1 POLARITYLine 1 polarity reversed

All Weil-McLain Boiler error codes →

Weil-McLain code CONFIGURATION: homeowner questions

What does Weil-McLain code CONFIGURATION mean?

Control board not configured. The control has not been set up for this boiler yet. The display is red and the boiler will not fire until the configuration is confirmed.

Is it safe to keep using my boiler with code CONFIGURATION?

It depends on the cause. The boiler has locked out or cannot run properly. One reset is fine; if the code comes back, it needs a licensed technician to find the cause.

Can I reset Weil-McLain code CONFIGURATION myself?

You can try one reset (power off for 30 seconds, then on). If Weil-McLain code CONFIGURATION comes back, the cause is still there and a licensed technician should check it.

Who can fix Weil-McLain code CONFIGURATION near me?

Aurora Star Tech Inc. repairs Weil-McLain boilers in Vaughan, Toronto and across the GTA. Call (647) 657-2977 or book a service call online.

Homeowner help: Boiler Not Heating: What to Check

Troubleshooting guides

Source: Weil-McLain CGa Series 4 Boiler Manual 550-100-223/0425, Table 11 Control fault information and troubleshooting, p.64. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.