Weil-McLain Boiler: Monthly piping, relief valve and air vent checks
Monthly piping, relief valve and air vent checks on a Weil-McLain boiler: Monthly inspection of piping, relief valve and automatic air vents.
Applies to: All boilers in this manual
Common causes of monthly piping, relief valve and air vent checks
- Leaks from fittings, circulators or relief valve
- Relief valve weeping
- Air vent not operating freely
How to fix monthly piping, relief valve and air vent checks: step by step
- Look for leaks around piping, circulators, relief valve and fittings; have any leak repaired right away by a qualified technician.
- Do not use petroleum-based cleaning or sealing compounds in the system.
- Check the relief valve and its discharge pipe for weeping or leakage.
- If the relief valve often weeps, contact a technician. Water boilers: suspect the expansion tank. Steam boilers: suspect a limit control set too high or system problems.
- Remove the cap from each automatic air vent and press the valve lightly with a screwdriver tip; it should move freely without leaking.
- Put the cap back on fully, then loosen it one turn so the vent can work.
- Have any vent that does not work correctly replaced.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Gas-Fired Boilers User Manual 550-100-226/0425, p. 18. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.