Weil-McLain Boiler: Vent damper installation requirements and steps

Updated · by Aurora Star Tech Inc.

Vent damper installation requirements and steps on a Weil-McLain boiler: The boiler will not run without its damper on the models that require one. Only the listed dampers in Table 19 (page 85) are approved for these Universal Control Systems.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: EG-30 to EG-75 and PEG-30 to PEG-65 with vent damper

How to fix vent damper installation requirements and steps: step by step

  1. Confirm the damper is required: EG-30 to EG-65 natural gas, PEG-30 to PEG-65 steam and natural gas, must have a damper. EG-75 natural gas may have one.
  2. Use only an approved damper from Table 19.
  3. Install the plug (supplied in the damper carton for 4" to 8" dampers) in the hole in the damper blade.
  4. Mount the damper directly on top of the draft hood so it serves only that boiler. Do not add other connections.
  5. Mount horizontally or vertically per the damper maker's instructions, with the blade indicator visible to the user.
  6. Keep screws or rivets from interfering with blade rotation.
  7. Run the damper harness between the actuator and the knockout in the jacket top panel. Use strain relief connectors and locknuts at both ends.
  8. Keep the harness clear of hot surfaces.
  9. Put the harness plug warning label where it stays visible after installation.
  10. Plug the damper harness receptacle into the harness plug.
  11. Set the damper hold-open switch to Automatic Operation.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

Source: EG/PEG Series 7 boiler manual, p. 18-19. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.