Weil-McLain Boiler: A sensor is missing from the list at power-up

Updated · by Aurora Star Tech Inc.

A sensor is missing from the list at power-up on a Weil-McLain boiler: When power comes on, the screen lists every sensor the control detects. A sensor that is not listed is not connected right.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: ECO Tec 80, 110, 150, 199 Series 3 (heat only)

Common causes of a sensor is missing from the list at power-up

  • Sensor not plugged in or loose wire
  • Sensor wired to the wrong terminals

How to fix a sensor is missing from the list at power-up: step by step

  1. Safety first: turn off power at the service switch before touching wiring. Gas-side work is for a qualified gas technician only.
  2. Turn power off and check the missing sensor's wiring.
  3. System return sensor goes on J19 pins 1-2, system supply sensor on J19 pins 3-4. The outdoor sensor also lands on J19 (see wiring diagram Figure 10).
  4. System supply and return sensors are required on primary/secondary piping. Put the supply sensor at least 6 pipe diameters but no more than 3 feet downstream of the boiler tee.
  5. The outdoor sensor ships with the boiler and is required unless the job is exempt.
  6. Turn power back on and check the list again.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

Source: Weil-McLain ECO Tec Series 3 Advanced Manual 550-100-600/1025, sec. Control action - Power up, p.3; Field wiring D/E, p.13. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.