Weil-McLain Boiler: External limit wiring for lockout and auto reset
External limit wiring for lockout and auto reset on a Weil-McLain boiler: External limits can be added to the U-Control. Manual reset limits require a manual reset from the control even after the limit closes. Automatic reset limits reset the control when the limit closes again. The factory jumper must be removed when these terminals are used.
Applies to: Ultra U-Control external limits
How to fix external limit wiring for lockout and auto reset: step by step
- For manual reset limits, wire the external limit across P13 terminals 1 and 2 and remove the factory jumper.
- For automatic reset limits, wire the external limit across P13 terminals 3 and 4 and remove the factory jumper.
- After a manual reset limit opens, the control locks out and activates the alarm contacts until reset.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain Ultra Series 4 boiler manual, p. 98. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.