Weil-McLain Boiler: Zoning two space heating zones with zone valves
Zoning two space heating zones with zone valves on a Weil-McLain boiler: Layout for two space heating zones using zone valves (120VAC or 24VAC) with a system circulator and no indirect DHW.
Applies to: Evergreen Pro control, two-zone space heating with zone valves and a system circulator
How to fix zoning two space heating zones with zone valves: step by step
- Review the 120VAC output and 24VAC input wiring pages (49 and 50).
- Wire space heating thermostats to INPUT 2, 3 and 4. INPUT 1 is reserved for the system circulator.
- Set System Settings 2, 3 and 4 to PRIORITY 2 and choose the space heating system type that matches the system.
- Keep the factory default settings for the heating system type, or change them if needed.
- Assign INPUT 1 to AUX PUMP/OUTPUT, then select INPUTS PRIORITY SETTING when prompted for when to activate the output.
- Confirm that Priority 2 RUN AUX PUMP/OUT is set to YES so the system pump runs when either zone calls for heat.
- Do not use J17-1/2 for a wired connection, because it drives the system circulator.
- Install a by-pass pressure regulating valve, because flow can occur with the zone valves closed.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain Series 2 Condensing Gas Boiler Advanced Manual, p. 61. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.