Weil-McLain Boiler: Outdoor sensor mounting and wiring
Outdoor sensor mounting and wiring on a Weil-McLain boiler: The outdoor sensor ships with the boiler. It is not required, but it must be installed to use WWSD or outdoor reset. Mount it out of direct sun and away from other heat or cooling sources. Thermostat wire is acceptable.
Applies to: Outdoor reset and WWSD
How to fix outdoor sensor mounting and wiring: step by step
- Mount the sensor on an exterior wall, shielded from sun and from heat or cooling sources.
- Connect the sensor leads to P10 terminals 1 and 2.
- Use thermostat wire if needed.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
More commissioning tips for boiler
Source: Weil-McLain Ultra Series 4 boiler manual, p. 98 and p. 99. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.