Weil-McLain Boiler: External high-limit and low water cutoff requirements
External high-limit and low water cutoff requirements on a Weil-McLain boiler: The U-Control provides high limit and low water protection by sensing the heat exchanger temperature. Some codes or jurisdictions require extra external controls. Use the external limit circuit on the P13 terminals when lower temperature circuits are on the system.
Applies to: All Ultra Series 4 models
How to fix external high-limit and low water cutoff requirements: step by step
- If ASME or Canadian requirements apply, install a manual reset high temperature limit in the supply piping between the boiler and isolation valve, set not above 200 °F.
- The U-Control shuts the boiler down at 195 °F, or lower if set lower.
- For a manual reset external limit, connect series isolated contacts to P13 terminals 1 and 2. For an automatic reset limit, use P13 terminals 3 and 4.
- If the U-Control is manual reset with an external manual reset limit, set the U-Control boiler limit at least 20 °F below the external limit. Example: 180 °F for a 200 °F external limit.
- If a low water cutoff is needed, install an electrode probe-type cutoff designed for water in a tee in the supply piping above the boiler. Wire it per the field wiring section.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Ultra Series 4 boiler manual, p. 9. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.