Weil-McLain Boiler: Vertical termination with separate vent and air pipes – location and clearances

Updated · by Aurora Star Tech Inc.

Vertical termination with separate vent and air pipes - location and clearances on a Weil-McLain boiler: Vertical termination layout. The air inlet ends in a down-turned 180-degree return bend and the vent in an up-turned coupling.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Ultra boilers using separate-pipe vertical terminations

How to fix vertical termination with separate vent and air pipes - location and clearances: step by step

  1. Set the air inlet edge at least 12 in above the roof or snow line.
  2. Set the vent top at least 12 in above the air intake to keep flue products out of the combustion air.
  3. Keep the vent at least 6 ft from adjacent walls and 5 ft below any roof overhang.
  4. Keep the vent at least 7 ft above any public walkway and at least 3 ft above any forced air intake within 10 ft.
  5. Keep the vent at least 12 in below or horizontally from any door, window or gravity air inlet.
  6. Keep the air inlet at least 12 in below the vent termination.
  7. Keep at least 4 ft horizontally from any electric meter, gas meter, regulator or relief valve.
  8. Space the roof penetrations for the air and vent pipes to meet the spacings in Figure 23. For multiple boilers, keep all vents at one height and all air pipes at one height.
  9. Use a galvanized thimble in the vent hole and flashing and sealing boots sized for the pipes. Vent hole must be at least 0.4 in larger than the vent pipe OD (2 3/4 in for 2 in, 4 in for 3 in, 5 in for 4 in).
  10. Do not terminate above any door or window.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

Source: Weil-McLain Ultra Series 4 boiler manual, p. 23-24. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.