Weil-McLain Boiler: Proof of closure interlock (flow switch or combustion air damper)
Proof of closure interlock (flow switch or combustion air damper) on a Weil-McLain boiler: A flow switch or combustion air damper (CAD) end switch can be wired as a proof-of-closure interlock. Doing so requires removing the factory jumper on connector J18. No control settings are needed for a flow switch. For a CAD interlock, the control should be set up so the damper opens whenever the boiler is called to fire.
Applies to: ECO Tec Series 3 80/110/150/199 (Combi and Heating Only)
How to fix proof of closure interlock (flow switch or combustion air damper): step by step
- Remove the jumper on connector J18 before wiring the external device.
- Wire the flow switch or CAD end switch to J18 as shown in the wiring diagram (Figure 76, page 78).
- For a CAD interlock, assign INPUT 3 as an AUX PUMP/OUTPUT function.
- Set the AUX PUMP/OUTPUT operating mode to local or System Damper so the damper runs on every call to fire.
- Wire the CAD motor to OUTPUT 3 (120VAC). If the damper motor needs another voltage or more current than the output allows, use an isolation relay.
- On multi-boiler installs, wire all proof-of-closure inputs in series with the end point devices and each boiler's closure switch input.
- Use only isolated dry contacts, because the J18 circuit carries 5 VDC.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: ECO Tec Series 3 boiler manual, p. 72. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.