Warming things up…Dialing in your comfort…Almost cozy…
Reliable Heating and Cooling Solutions – Quality Service, Fair Prices, Guaranteed Satisfaction!

Weil-McLain Boiler: Commissioning check-out highlights before handover

Updated · by Aurora Star Tech Inc.

Commissioning check-out highlights before handover on a Weil-McLain boiler: Key verifications from the startup checklist. Complete full checklist and certificate on page 140.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Ultra Series 4 startup

How to fix commissioning check-out highlights before handover: step by step

  1. Confirm the U-Control is set for the correct boiler model and installation date/contact entered.
  2. Confirm boiler and heat distribution units are filled, water chemistry is verified, and inhibitor added.
  3. Purge air from system and from gas piping; check gas piping for leaks; confirm condensate trap is primed.
  4. Confirm propane orifice and propane conversion label if firing propane.
  5. Check thermostat circuit wiring for stray voltages.
  6. Verify burner flame and combustion per page 40.
  7. Verify space heating and DHW control operation; test any field-installed limits or low water cutoff for proper lockout.
  8. Cycle the boiler with the thermostat at highest and lowest settings and confirm startup and shutdown.
  9. Measure natural gas input and check incoming gas pressure (see gas pressure setting).
  10. Observe several operating cycles, set room thermostat, and fill out the Installation and Service Certificate.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

Source: Ultra Series 4 gas-fired water boiler manual, p. 42. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.

Emergency Boiler Repair