Weil-McLain Boiler: Check flue gas temperature
Check flue gas temperature on a Weil-McLain boiler: Flue temperature check at high fire.
Applies to: SVF 1500-3000 Series 1 boiler
Common causes of check flue gas temperature
- Heat exchanger fouled
How to fix check flue gas temperature: step by step
- Set the boiler to high fire.
- On the control display, view flue gas temperature and boiler return temperature.
- Flue gas should be no more than 30°F above boiler return temperature.
- If higher, shut down, let the boiler cool, and clean the heat exchanger (page 108).
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain SVF Series 1 boiler manual, p. 98. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.