Weil-McLain Boiler: Install sidewall direct vent with separate pipes
Install sidewall direct vent with separate pipes on a Weil-McLain boiler: Vent and air pipes run through two separate sidewall openings. The layout must meet the termination clearances.
Applies to: Sidewall direct vent, separate pipes
How to fix install sidewall direct vent with separate pipes: step by step
- Confirm the boiler location lets vent and air pipe run to the chosen sidewall spot.
- Check the sidewall location against the termination clearance figure before cutting.
- Use only listed vent materials and adapters. Stay within the maximum vent and air lengths.
- Cut the penetrations and install the sidewall plates as described.
- Slope horizontal piping down toward the boiler at least 1/4 in per foot.
- Support pipe every 5 ft on horizontal and vertical runs, with a hanger within 6 in of any upturn.
- Fit the air pipe with a down-turned elbow and the vent pipe with an elbow pointed away from the air inlet.
- Keep the air coupling at least 12 in below the vent termination and at least 12 in above grade or snow line.
- If an external pipe is longer than 4 ft, enclose it in insulation so condensate cannot freeze in it.
- Brace external pipes no more than 24 in apart and keep all clearances.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: ECO Tec Series 3 boiler manual, p. 33-34. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.