Weil-McLain Boiler: Add antifreeze to the system
Add antifreeze to the system on a Weil-McLain boiler: Use only antifreeze listed by WM Technologies for ECO Tec boilers.
Applies to: ECO Tec Series 3 80/110/150/199
How to fix add antifreeze to the system: step by step
- Determine the freezing temperature needed for the lowest likely water temperature.
- Find the antifreeze concentration by volume for that temperature from the manufacturer's data.
- Add up the total water volume of system piping and components, including the expansion tank and boiler.
- Multiply the total volume by the antifreeze percent to get gallons of antifreeze.
- Do not exceed 50% antifreeze by volume.
- Flush any system that used glycol before installing the boiler.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: ECO Tec Series 3 Condensing Gas Boiler Boiler Manual, p. 130. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.