Weil-McLain Boiler: Remote modulation setup with 0-10VDC input

Updated · by Aurora Star Tech Inc.

Remote modulation setup with 0-10VDC input on a Weil-McLain boiler: A 0-10VDC signal drives boiler modulation. Input 2 must be changed to a 0-10V source after the Wizard is done.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Evergreen 110/155/220/299/300/399

How to fix remote modulation setup with 0-10vdc input: step by step

  1. Wire the 0-10VDC positive signal to J16 terminal 6 and the common to terminal 5.
  2. Do not wire anything to Input 2.
  3. After the Wizard is complete, open the System Settings menu, select INPUT 2, and change SOURCE to 0-10v.
  4. Confirm OUTPUT 2 switches on and off with the heat demand.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

Source: Weil-McLain Series 2 Condensing Gas Boiler Advanced Manual, p. 54. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.