Weil-McLain Boiler: Remote modulation setup with 0-10VDC input
Remote modulation setup with 0-10VDC input on a Weil-McLain boiler: A 0-10VDC signal drives boiler modulation. Input 2 must be changed to a 0-10V source after the Wizard is done.
Applies to: Evergreen 110/155/220/299/300/399
How to fix remote modulation setup with 0-10vdc input: step by step
- Wire the 0-10VDC positive signal to J16 terminal 6 and the common to terminal 5.
- Do not wire anything to Input 2.
- After the Wizard is complete, open the System Settings menu, select INPUT 2, and change SOURCE to 0-10v.
- Confirm OUTPUT 2 switches on and off with the heat demand.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain Series 2 Condensing Gas Boiler Advanced Manual, p. 54. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.