Weil-McLain Boiler: Check ignition system safety shutoff device
Check ignition system safety shutoff device on a Weil-McLain boiler: Confirm the ignition safety device locks out when there is no fuel.
Applies to: ECO Tec Series 3 gas boilers
Common causes of check ignition system safety shutoff device
- No gas reaches the burner during the test (manual gas valve closed)
How to fix check ignition system safety shutoff device: step by step
- Turn off the boiler.
- Close the manual gas valve on the gas line.
- Turn the boiler on. It will attempt ignition but will not light, then lock out and show Ignition Fault 1.
- Clear the lockout by selecting Manual Reset on the Homeowner screen menu.
- Open the manual gas valve to restore fuel supply.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: ECO Tec series 3 boiler manual, p. 136. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.