Weil-McLain Boiler: No flame detected during ignition
No flame detected during ignition on a Weil-McLain boiler: If no flame is detected, the gas valve closes, the blower runs postpurge, and the control starts the cycle again. After 5 failed attempts the control waits 60 minutes before retrying. A flashing display means a lockout condition.
Applies to: All Ultra models with U-Control
How to fix no flame detected during ignition: step by step
- Watch for the display to turn red when an error or limit event occurs.
- If the display flashes, note the three screens it cycles through (Figure 124, page 117) for the lockout detail.
- Check the gas supply and inlet pressure per the gas pressure limits in this manual.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain Ultra Series 4 boiler manual, p. 32. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.