Weil-McLain Boiler: Boiler relief valve testing and replacement
Boiler relief valve testing and replacement on a Weil-McLain boiler: Keep the relief valve working. Replace it if it weeps or will not seat. Do not set the boiler limit control above 10 PSIG.
Applies to: EG and PEG Series 7 boilers
Common causes of boiler relief valve testing and replacement
- Valve weeping or not seating
- Corrosion or deposits in the valve body
- Limit control set above 10 PSIG
How to fix boiler relief valve testing and replacement: step by step
- Before testing, confirm the discharge pipe is connected to the valve outlet and arranged to safely dispose of discharge. Wear gloves.
- Test the relief valve at least monthly during the heating season to confirm the valve and discharge piping flow freely. Test more often if corrosion or deposits are seen.
- With the system at operating pressure, lift and hold the test lever fully open for at least 5 seconds, then release it and let the valve snap shut (try lever test).
- Perform the try lever test at the end of any non-service period.
- If the valve weeps or will not seat properly, replace it.
- Have a licensed plumbing contractor or authorized inspection agency reinspect the relief valve at least once every three years. This is not an owner task.
- Check the boiler limit control setting. It should never be set above 10 PSIG.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain EG/PEG Series 7 Boiler Manual, p. 71. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.