Weil-McLain Boiler: Vent and air pipe support, slope and clearance
Vent and air pipe support, slope and clearance on a Weil-McLain boiler: Support and slope requirements for vent and air piping runs.
Applies to: Ultra vent and air piping
How to fix vent and air pipe support, slope and clearance: step by step
- Support pipe every 5 feet on horizontal and vertical runs.
- Install a hanger within 6 inches of any upturn in the piping.
- Slope vent and air piping back toward the boiler at least 1/4 inch per foot of run.
- Do not allow sags anywhere in the run.
- Keep at least 3/16 inch clearance between the vent pipe and any combustible wall or material.
- Support vertical runs outside the building with brackets as shown in the termination instructions.
- Use long-radius elbows on air piping when using 2-inch or 3-inch pipe to reduce pressure drop.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain Ultra Series 4 boiler manual, p. 90-92. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.