Weil-McLain Boiler: DHW tank connection options
DHW tank connection options on a Weil-McLain boiler: A DHW tank can be piped direct to the boiler or treated as a zone, depending on the layout.
Applies to: SVF 1500-3000 Series 1
How to fix dhw tank connection options: step by step
- For direct connection, pipe from the near-boiler piping to the DHW tank's boiler connections as shown.
- For DHW as a zone, only do this if no DHW tank is already connected to the boiler.
- For DHW as a zone, use the Advanced Manual to set the boiler pump to run during DHW demands, and set TARGET MOD SENSOR to System Supply.
- DHW as a zone is not recommended for radiant or chilled water applications.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SVF Series 1 boiler manual, p. 17-23. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.