Weil-McLain Boiler: Check burner flame
Check burner flame on a Weil-McLain boiler: Inspect the flame through the observation window at high and low fire.
Applies to: ECO Tec Series 3 gas boilers
Common causes of check burner flame
- Dirty or blocked burner
- Combustion out of adjustment
How to fix check burner flame: step by step
- Inspect the flame through the window at high fire and at low fire (procedure p. 133).
- If flame is poor, check combustion values.
- If combustion is correct, turn off the boiler and let it cool.
- Remove the burner and clean it with a vacuum or compressed air (do not use compressed air indoors).
- Remove the cover plate to access the burner (p. 151).
- If replacing the burner, make sure the burner gasket is in good condition and correctly placed.
- Restart and inspect again at high and low fire.
- If flame is still poor and combustion is correct, get a replacement burner from WM Technologies.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: ECO Tec series 3 boiler manual, p. 142. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.