Weil-McLain Boiler: Adjust gas valve throttle screw to correct combustion
Adjust gas valve throttle screw to correct combustion on a Weil-McLain boiler: Only for a qualified technician using calibrated combustion test instruments. Do not adjust the throttle screw at low fire; only check low fire values.
Applies to: Models 80/105 (Figure 39), 155/230/299 (Figure 40), 399 (Figure 41)
Common causes of adjust gas valve throttle screw to correct combustion
- Difficulty igniting
- Poor flame stability at low fire
- Combustion noise
- High CO values
- CO2 outside Figure 42 range at high fire
How to fix adjust gas valve throttle screw to correct combustion: step by step
- Set Manual test mode to MAX (high fire) and let the boiler stabilize, then read CO2.
- If CO2 is high, turn the throttle screw clockwise to lower input. Let it stabilize and read again. Repeat until the target is reached.
- If CO2 is low, turn the throttle screw counterclockwise to raise input. Let it stabilize and read again. Repeat until the target is reached.
- Lock the boiler at low fire and check readings. If acceptable, verify high fire again.
- Return firing rate to AUTO.
- If acceptable values cannot be reached for both high and low fire, contact the WM Technologies representative.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Ultra Series 4 gas-fired water boiler manual, p. 41. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.