Weil-McLain Boiler: 3-way valve test (combi models only)
3-way valve test (combi models only) on a Weil-McLain boiler: Tests whether the DHW/heating 3-way valve actuator moves and the valve shaft works.
Applies to: Combi models 110, 150, 199
How to fix 3-way valve test (combi models only): step by step
- Go to DIAGNOSTICS, Manual Test Mode.
- Make sure the boiler is in Standby with no heat calls active.
- Press edit and select the desired 3-way valve position.
- Remove the actuator (procedure in Figure 138, p. 158) and watch the motor shaft as you change position.
- The shaft should slide in and out with no play in the extended position.
- Push the shaft in the sanitary shutter with a blunt object; it should compress against the valve spring.
- If the shaft will not move or sticks compressed, follow the flow manifold cleaning procedure on p. 158.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
More service & test modes tips for boiler
Source: ECO Tec series 3 boiler manual, p. 143. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.