Size natural gas supply piping on a Weil-McLain boiler: Sizing method for natural gas piping from the meter to the boiler entrance.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Natural gas supply piping

How to fix size natural gas supply piping: step by step

  1. Size the gas supply from the meter outlet to the boiler entrance using the pipe capacity and fitting tables.
  2. Add the total input of all connected appliances in Btuh and divide by 1,000 to get approximate cubic feet per hour.
  3. Add equivalent fitting lengths to the actual straight pipe run before reading the capacity table.
  4. Confirm the calculation is for natural gas at specific gravity 0.60 and 0.30 in w.c. drop.
  5. Check local codes (ANSI Z223.1/NFPA 54 or CAN/CSA B149.1) for further sizing rules.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

Source: SVF Series 1 boiler manual, p. 48. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.