Weil-McLain Boiler: Connecting PVC/ABS vent or air pipe to the boiler adapter
Connecting PVC/ABS vent or air pipe to the boiler adapter on a Weil-McLain boiler: Vent and air pipe connect to the boiler with a clamped adapter that seals on an internal gasket. The clamp only holds the pipe.
Applies to: Ultra vent and air connections
How to fix connecting pvc/abs vent or air pipe to the boiler adapter: step by step
- Clean and chamfer the insertion end of the pipe and deburr its inside edge.
- Deburr and clean the inside and outside of the other end.
- Check the adapter for obstructions or foreign objects.
- Loosen the adapter clamp screw.
- Mark the pipe 3-1/2 inches from its end with a felt-tip pen.
- Put a small amount of silicone grease on the pipe end.
- Insert the pipe into the adapter and slide it down to the 3-1/2 inch mark.
- Tighten the clamp securely without overtightening, since the internal gasket provides the seal.
- Do not force or bend the adapter or pipe during insertion.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain Ultra Series 4 boiler manual, p. 91. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.