Updated · by Aurora Star Tech Inc.

Boiler will not fire with a flow switch or damper on J18 on a Weil-McLain boiler: The proof-of-closure circuit on J18 comes with a jumper. A flow switch or combustion air damper end switch can replace it, and the boiler only fires when that contact is closed.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: ECO Tec 80, 110, 150, 199 Series 3 (heat only)

Common causes of boiler will not fire with a flow switch or damper on j18

  • Flow switch or damper end switch not closing
  • Contact not isolated (the circuit runs on 5 VDC)
  • Damper not driven because Input/Output 3 is not set up

How to fix boiler will not fire with a flow switch or damper on j18: step by step

  1. Safety first: turn off power at the service switch before touching wiring. Gas-side work is for a qualified gas technician only.
  2. If nothing is wired there, the J18 jumper must be in place.
  3. The device must give an isolated contact; J18 carries 5 VDC. J18-1 has a PTC that trips at 340 mA (140 mA hold at 20°C).
  4. Flow switch: no control settings needed.
  5. Damper: assign Input 3 as AUX Pump/Output, mode local or System Damper. Output 3 then gives 120 VAC to the damper motor. Use a relay for other voltages or over 2.2 A.
  6. Multi-boiler system damper: proof-of-closure inputs wired in series with the end devices. Local damper: wire each boiler's input on its own, not in series.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

Source: Weil-McLain ECO Tec Series 3 Advanced Manual 550-100-600/1025, sec. Field wiring J. Proof of closure, p.15. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.