Weil-McLain Boiler: Piping multiple boilers to Easy-Fit manifolds
Piping multiple boilers to Easy-Fit manifolds on a Weil-McLain boiler: Connect the boilers to the main header through Easy-Fit manifolds, with manifold layout and flow direction set per the piping figures.
Applies to: Multiple Evergreen boilers using Easy-Fit manifolds
How to fix piping multiple boilers to easy-fit manifolds: step by step
- Size the system piping for the flow and install tees on the main for the manifolds.
- Connect the manifold to the main as close as practical to the midpoint of the boilers, within 8 pipe diameters.
- Use tees for 4 or fewer boilers. Use tees or crosses for 5 or more boilers.
- Put the return manifold on the return side of the main and the supply manifold on the supply side.
- Reverse the short and long ends of the manifolds to alternate supply and return spacing.
- Pipe the first boiler off the return manifold to the furthest connection on the supply manifold from the main header.
- Install an isolation valve on the supply and return of each boiler.
- Install the main air eliminator and primary circulator on the supply piping, and the expansion tank on the suction side of the system circulator.
- Strap system supply and return sensors at least 6 pipe diameters (no more than 3 feet) from the boiler tees.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain Evergreen Series 2 advanced manual, p. 6-7. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.