Weil-McLain Boiler: Display blank but boiler operating
Display blank but boiler operating on a Weil-McLain boiler: Communication lost between the U-Control and the display.
Applies to: Ultra 80, 105, 155, 230, 299, 399
Common causes of display blank but boiler operating
- Loose connection or poor pin engagement at plug P9 or the display board
- Broken wire in the harness from display to U-Control
- Failed display module
How to fix display blank but boiler operating: step by step
- Check plug P9 on the U-Control and the back of the display board for loose connections and proper pin alignment.
- Check continuity on the wire harness from the display to the U-Control.
- Cycle power using the boiler power switch and check operation.
- If still faulty, replace the display module (see repair parts section).
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Ultra Series 4 gas-fired water boiler manual, p. 119. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.