Warming things up…Dialing in your comfort…Almost cozy…
Reliable Heating and Cooling Solutions – Quality Service, Fair Prices, Guaranteed Satisfaction!

Weil-McLain Boiler: Example F field wiring between master and shadow boilers

Updated · by Aurora Star Tech Inc.

Example F field wiring between master and shadow boilers on a Weil-McLain boiler: Wiring layout for the master and shadow boilers, including sensors, zone outputs and valves.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Example F multi-boiler wiring, Figures 18 and 19 context

How to fix example f field wiring between master and shadow boilers: step by step

  1. Connect the master boiler and each shadow boiler in the order shown: master to shadow 2, shadow 2 to shadow 3, and shadow 3 to shadow 4.
  2. On each boiler, wire the zone thermostats to the zone inputs and the zone circulators or valves to the matching numbered outputs.
  3. Wire the boiler isolation valve (item 17a) to output 4 on the master and each shadow that uses it.
  4. On shadow 3, wire the bypass valve (item 17b) to output 3.
  5. Wire the outdoor air sensor, system supply sensor and system return sensor to the J19 or J16/J17 terminals as shown in the diagram. Sensors marked * are for redundancy only and are not required.
  6. Check that each boiler's 120 VAC outputs stay within 2.2 A and use an external relay where the valve or load needs it.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

Source: Weil-McLain Series 2 advanced manual 550-100-581/0325, p. 42-43. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.