Weil-McLain Boiler: Boiler circulator relay rating
Boiler circulator relay rating on a Weil-McLain boiler: The expansion module relay that drives the boiler pump has a 10 A maximum rating.
Applies to: Boiler circulator wiring
How to fix boiler circulator relay rating: step by step
- Use external 120VAC single phase power for the pump, sized for the pump load.
- Interrupt the pump hot line or enable circuit at the EP7 rear terminal block.
- Keep the pump load within the 10 A relay limit.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SVF Series 1 boiler manual, p. 49. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.