Weil-McLain Boiler: Vertical vent with sidewall air termination
Vertical vent with sidewall air termination on a Weil-McLain boiler: Use a sidewall air inlet with a vertical vent through the roof.
Applies to: SVF 1500-3000 vertical vent with sidewall air
How to fix vertical vent with sidewall air termination: step by step
- Cut the air pipe hole to the air pipe maker's size.
- Cut and thimble the vent hole as for vertical terminations.
- Fit corrosion-resistant stop plates from the vent pipe maker, with holes just larger than the air pipe diameter.
- Insert the last air pipe length from outside until its female shoulder rests on the outer stop plate.
- Insert the down-turned 90 degree air termination elbow into the air pipe end.
- Install a bird screen in the vent termination elbow.
- Seal all exterior openings with exterior caulk.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SVF Series 1 boiler manual, p. 44-45. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.