Weil-McLain Boiler: External limit lockout and automatic restart
External limit lockout and automatic restart on a Weil-McLain boiler: External limits can be wired for manual reset or automatic reset. Manual reset locks the control out and requires a manual reset. Automatic reset restarts the burner after the limit closes.
Applies to: Optional external limit circuits
Common causes of external limit lockout and automatic restart
- External limit on manual reset circuit (P13 #1 and #2) opened
- External limit on automatic reset circuit (P13 #3 and #4) opened
How to fix external limit lockout and automatic restart: step by step
- Remove the factory jumper before connecting an external limit.
- For manual reset, wire isolated limit contacts to P13 #1 and #2.
- For automatic reset, wire isolated limit contacts to P13 #3 and #4.
- On a manual reset lockout, close the limit and reset the control at the boiler. Cycling power will not clear it.
- On automatic reset, the burner restarts 150 seconds after the limit closes.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SVF Series 1 boiler manual, p. 61. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.