Weil-McLain Boiler: Vent fittings and reducers
Vent fittings and reducers on a Weil-McLain boiler: Fitting rules for vent and air piping. Use sweep elbows only and reducers in place of bushings.
Applies to: All Ultra vent and air piping
How to fix vent fittings and reducers: step by step
- Use sweep elbows only in vent and air piping. Do not use short-radius elbows.
- When stepping down from 4 in to 3 in or 3 in to 2 in, use a tapered reducer with a PVC nipple at least 6 in long.
- Do not use a bushing. A bushing will not seal in the boiler flue/exhaust adapter.
- Put a 3x2 reducer at the boiler and at the termination for 2 in runs; put a 4x3 reducer at the boiler and at the termination for 3 in runs.
- Do not mix plastic piping types. Do not use cellular core pipe.
- Stainless AL29-4C vent: install a PVC-to-stainless adapter at the boiler, and at the termination unless using separate-pipe termination.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain Ultra Series 4 boiler manual, p. 18-19. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.