Weil-McLain Boiler: Install boiler relief valve and discharge piping
Install boiler relief valve and discharge piping on a Weil-McLain boiler: The relief valve must be on the top boiler pipe only, not the boiler out, and must be above the heat exchanger. The discharge line has to be piped to a safe location.
Applies to: All ECO Tec Series 3 piping layouts
Common causes of install boiler relief valve and discharge piping
- Relief valve connected to the boiler out
- Shutoff valve installed between relief valve and boiler or in the discharge line
How to fix install boiler relief valve and discharge piping: step by step
- Install the relief valve in a ¾" street elbow with a ¾" tee onto the top water pipe (Figure 12, page 18).
- Install the valve only with the spindle vertical.
- Run the discharge line to a safe disposal point, pitched downward from the valve, ending at least 6" above a floor drain where discharge is visible.
- Keep the discharge line as short as possible and the same size as the valve outlet along its length.
- Terminate the discharge plain, not threaded, in material rated for 375°F or greater.
- Do not pipe the discharge where freezing could occur, and do not install a shutoff valve or any obstruction in the line.
- After filling and pressurizing, lift the lever to test. If the valve does not discharge freely, replace it.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: ECO Tec Series 3 boiler manual, p. 58. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.