Weil-McLain Boiler: Breeching installation rules
Breeching installation rules on a Weil-McLain boiler: Sizing and slope rules for the breeching from the draft hood or damper outlet to the chimney or vent.
Applies to: All Series 7 boilers
How to fix breeching installation rules: step by step
- Use breeching the same size as the draft hood or damper outlet.
- Run vertical to the outside where possible for best performance.
- For horizontal runs, slope upward at least 1/4 in. per lineal foot toward the chimney or vent.
- Support horizontal breeching with hangers to prevent sagging.
- Do not connect the breeching to any part of a mechanical draft system under positive pressure.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: EG/PEG Series 7 boiler manual, p. 19. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.