Circulator and air separator placement on a Weil-McLain boiler: The circulator is supplied by the installer, but wiring is provided with the boiler. Locate it in return or supply piping as needed.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: EG water boilers, forced hot water systems

How to fix circulator and air separator placement: step by step

  1. Supply the circulator separately. Wiring is in the boiler, so it can go in return or supply piping.
  2. Pipe the expansion tank to the suction side of the circulator when possible.
  3. Install an air separator in the supply piping.
  4. Connect the expansion tank to the air separator only if the separator is on the circulator suction side.
  5. Make the system fill connection at the same point as the expansion tank connection.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

More commissioning tips for boiler

Source: EG/PEG Series 7 boiler manual, p. 20. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.

Emergency Boiler Repair

647-657-2977