Weil-McLain Boiler: Clean boiler heating surfaces
Clean boiler heating surfaces on a Weil-McLain boiler: Remove soot and boiler cement buildup from the heating surfaces and collector hood.
Applies to: EG and PEG Series 7 boilers
Common causes of clean boiler heating surfaces
- Soot in the flue or on the heating surfaces
- Boiler cement buildup on collector hood and sections
How to fix clean boiler heating surfaces: step by step
- Follow the shut-down procedure.
- Disconnect the breeching and remove the damper (if used) and draft hood.
- Remove the upper rear jacket panel and turn back the jacket insulation to expose the collector hood.
- Remove the collector hood. Clean excess boiler cement from the hood and cast iron sections.
- Remove the burners from the base of the boiler and clean them per the main burner procedure. Place newspaper in the base to catch soot.
- Clean between the sections with a wire flue brush.
- Remove the paper and soot. Vacuum or brush the base and surrounding area.
- Replace the collector hood and seal it with boiler cement.
- Replace the draft hood, damper (if used) and breeching.
- Replace the insulation and jacket panel.
- Replace the main burners.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain EG/PEG Series 7 Boiler Manual, p. 71. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.