Weil-McLain Boiler: Boiler does not start – initial checks
Boiler does not start – initial checks on a Weil-McLain boiler: Work through these checks before going to the troubleshooting section.
Applies to: EG / PEG water boilers
Common causes of boiler does not start – initial checks
- Loose connection, blown fuse or service switch off
- Boiler temperature setpoint set below boiler water temperature
- Thermostat set below room temperature
- Gas not turned on at meter or boiler
- Incoming gas pressure below 5 in. w.c. for natural gas
How to fix boiler does not start – initial checks: step by step
- Check for loose connections, a blown fuse or the service switch in the off position.
- Set the boiler temperature above the boiler water temperature.
- Set the thermostat above room temperature.
- Confirm gas is on at the meter and at the boiler.
- Confirm incoming gas pressure is at least 5 in. w.c. for natural gas.
- If none of these corrects the problem, see Troubleshooting 1 on page 73.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: EG / PEG Series 7 boiler manual, p. 59. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.