Weil-McLain Boiler: System supply and return sensor placement
System supply and return sensor placement on a Weil-McLain boiler: Two strap-on sensors ship with the boiler and can attach to pipe up to 3 inches in diameter. The supply sensor must be at least six pipe diameters but no more than 3 feet downstream of the boiler connection. The return sensor is used for display and for sensor-failure checks. For multiple boilers, the lead boiler needs both sensors.
Applies to: Ultra U-Control system temperature sensing
How to fix system supply and return sensor placement: step by step
- Strap the system supply sensor on the main piping at least six pipe diameters, and no more than 3 feet, downstream of the boiler connection.
- Strap the system return sensor on the return piping.
- For multiple boiler applications, wire both sensors to the LEAD boiler.
- Confirm the sensors are wired with thermostat wire or equivalent.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
More commissioning tips for boiler
Source: Weil-McLain Ultra Series 4 boiler manual, p. 98 and p. 11. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.