Weil-McLain Boiler: Outdoor reset operation
Outdoor reset operation on a Weil-McLain boiler: Outdoor reset adjusts supply target temperature to outdoor temperature. Max target is for design maximum heat loss. Min target is the supply temperature used when outdoor temperature is above the outdoor temp for min target. Outdoor temp for max target should equal the site design outdoor temperature.
Applies to: Space heating priorities with outdoor sensor
How to fix outdoor reset operation: step by step
- Set the desired space heating zone temperatures.
- Set MAX TARGET TEMP to the design supply water temperature (typically 180°F for finned tube baseboard on new installs).
- Set MIN TARGET TEMP to the lowest acceptable supply temperature; do not set it below the outdoor temp for min target unless heating performance loss is acceptable.
- Set OUTDOOR TEMP FOR MIN TARGET and OUTDOOR TEMP FOR MAX TARGET to match the site (factory defaults are 70°F and 0°F).
- Make these settings in the priority menu for the system.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Series 2 Advanced Manual, p. 10. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.