Boiler: No heat or some zones cold
No heat or some zones cold on a boiler: Boiler fires but a zone stays cold, or the boiler won't fire at all. Two different problems, so sort out which one you have first.
Applies to: Hydronic boilers
Common causes of no heat or some zones cold
- Low system pressure, which also trips the low water cutoff on some boilers
- Air in the system, a zone airlocked and no flow
- Failed circulator pump or zone valve that will not open
- Thermostat or zone control wiring fault, so the call for heat never arrives
- Boiler in lockout
How to fix no heat or some zones cold: step by step
- Check the boiler display or LED for an error code, because a lockout needs the code, not guesswork
- Check system pressure (typically 12 to 20 psi cold on residential systems; confirm for the installation), low pressure means find the leak or fill
- Bleed air from radiators or purge the zone, because an airlocked zone gets no flow
- Confirm the circulator runs and the zone valve opens when the zone calls, feel the pipes and watch the valve end switch
- Check thermostat and zone control wiring, meter 24 V at the zone controller when the stat calls
- If the boiler is in lockout, reset once only and call a licensed tech if it comes back
If the unit shows an error code, look it up: Beckett Boiler codes Bosch Boiler codes Glow Brand Boiler codes HTP Boiler codes KWE Boiler codes Navien Boiler codes NTI Boiler codes Rinnai Boiler codes Viessmann Boiler codes Weil-McLain Boiler codes
Source: General HVAC service practice — verify per model. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.