Weil-McLain Boiler: 0-10VDC output for lead/lag and variable speed pump

Updated · by Aurora Star Tech Inc.

0-10VDC output for lead/lag and variable speed pump on a Weil-McLain boiler: The 0-10VDC output can drive lead/lag systems or a variable speed boiler pump.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Evergreen 110/155/220/299/300/399

How to fix 0-10vdc output for lead/lag and variable speed pump: step by step

  1. For lead/lag, set MAX RATE VOLTS and MIN RATE VOLTS to the desired output range.
  2. The output only works when AHD is in use, an AHD call is active, Temp Dependent is set to Yes, and valid sensors are present.
  3. For a variable speed pump, connect the output to the pump's 0-10VDC input.
  4. Set VARIABLE SPEED MAX RATE VOLTS for high fire, VARIABLE SPEED MIN RATE VOLTS for low fire, and VOLTS WHEN BURNER OFF for burner-off operation.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

Source: Weil-McLain Series 2 Condensing Gas Boiler Advanced Manual, p. 54. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.