Weil-McLain Boiler: Multiple boiler vent/air terminations
Multiple boiler vent/air terminations on a Weil-McLain boiler: Several Ultra boilers on one roof or wall need matched terminations and minimum spacing. Wrong heights or spacing can cause severe injury, death or property damage.
Applies to: Multiple Ultra boilers sharing roof or wall terminations
How to fix multiple boiler vent/air terminations: step by step
- Terminate all vent pipes at the same height and all air pipes at the same height.
- Place roof penetrations for at least 12 in between the edge of an air intake elbow and the adjacent boiler's vent pipe (US installations; see Figure 23).
- In Canada, meet the clearances in CAN/CSA B149.1 or B149.2.
- Treat the Ultra air inlet as part of a direct vent connection, not as a forced air intake, for spacing from adjacent boiler vents.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain Ultra Series 4 boiler manual, p. 24. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.