Weil-McLain Boiler: Adjust low fire CO2 at the offset screw

Updated · by Aurora Star Tech Inc.

Adjust low fire CO2 at the offset screw on a Weil-McLain boiler: Set the low fire CO2 using the offset regulating screw under the 4mm cap.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: ECO Tec Series 3 gas boilers

How to fix adjust low fire co2 at the offset screw: step by step

  1. Set the boiler to LOW (minimum output) and let it stabilize.
  2. Check the blower rpm against the table in Figure 125, 126 or 127 (p. 145-147).
  3. Remove the 4mm Allen head cap (see Figure 120, p. 135).
  4. If CO2 is high, turn the offset screw counterclockwise to lower the input.
  5. If CO2 is low, turn the offset screw clockwise to raise the input.
  6. Let the boiler stabilize and read again. Repeat until the target CO2 is reached.
  7. Confirm CO is within limits.
  8. Reinstall the 4mm cap when adjustment is complete.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

Source: ECO Tec series 3 boiler manual, p. 136. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.