Weil-McLain Boiler: Aluminum heat exchanger water chemistry
Aluminum heat exchanger water chemistry on a Weil-McLain boiler: The Ultra heat exchanger is aluminum. System pH must stay between 7.0 and 8.5 and water chemistry must be checked. Chemical treatment may be needed. Sediment and scale can damage the heat exchanger, and fresh make-up water shortens boiler life.
Applies to: Ultra Series 4 boilers
How to fix aluminum heat exchanger water chemistry: step by step
- Flush the system thoroughly before connecting the boiler to remove sediment.
- Install a strainer or other sediment removal if needed.
- Check water pH and chemistry and treat as needed (see page 35).
- Repair leaks at once to stop make-up water from entering.
- Use the boiler only in a closed-loop system.
- Do not add cold water to a hot boiler.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain Series 4 gas-fired water boiler manual, p. 4. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.