Checking the boiler out sensor on a Weil-McLain boiler: Check the boiler out resistance-type sensor against Table 16 and confirm the control reads it correctly.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: EG and PEG Series 7 water boilers

How to fix checking the boiler out sensor: step by step

  1. Turn off all power to the boiler before servicing.
  2. Measure sensor resistance with an ohmmeter in water at known temperatures: 32°F (freezing), room temperature, and 212°F (sea-level boiling). Insert the sensor in the water for the freezing and boiling points.
  3. Compare each reading with the expected range in Table 16.
  4. To check the control, temporarily connect a resistance decade box in place of the sensor and confirm the control display shows the matching temperature.
  5. Do not leave jumpers or bypasses installed after testing.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

Source: EG / PEG Series 7 Boiler Manual, p. 73. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.