Weil-McLain Boiler: Steam boiler water chemistry limits
Steam boiler water chemistry limits on a Weil-McLain boiler: Chlorides above 200 ppm accelerate water-side corrosion. Treatment should be considered if chloride in makeup water is above 30 ppm. Chloride above 400 ppm or TDS above 1000 ppm requires drain and refill.
Applies to: EG / PEG steam boilers
How to fix steam boiler water chemistry limits: step by step
- If chloride is above 200 ppm, expect accelerated water-side corrosion and consider treatment.
- If makeup water chloride is above 30 ppm, consider boiler water treatment.
- If there is no chemical treatment and chloride is above 400 ppm or TDS is above 1000 ppm, drain and refill with fresh water.
- After refilling, bring the boiler to pressure for 15 minutes to drive off excess oxygen.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: EG / PEG Series 7 boiler manual, p. 61-62. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.