Weil-McLain Boiler: Install system supply and return temperature sensors

Updated · by Aurora Star Tech Inc.

Install system supply and return temperature sensors on a Weil-McLain boiler: Recommended for primary/secondary piping. Required for proper control.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: ECO Tec Series 3 primary/secondary systems

How to fix install system supply and return temperature sensors: step by step

  1. Use two strap-on sensors (separate kit). For pipe larger than 5 in. or non-metallic pipe, use immersion sensors.
  2. Attach one sensor to the system supply piping and one to the system return piping.
  3. Locate the supply sensor at least six pipe diameters, but no more than 3 ft, downstream from the boiler connection.
  4. Wire the return sensor to J19 pins 1 and 2.
  5. Wire the supply sensor to J19 pins 3 and 4.
  6. Thermostat wire can be used for the sensor leads.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

Source: ECO Tec series 3 condensing gas boiler boiler manual, p. 70. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.

Emergency Boiler Repair

647-657-2977