Weil-McLain Boiler: Do not common vent: removing an old boiler from a common vent

Updated · by Aurora Star Tech Inc.

Do not common vent: removing an old boiler from a common vent on a Weil-McLain boiler: The SVF cannot share a common vent with any other appliance, and it cannot use an existing common vent. Removing the old boiler can leave remaining appliances on an oversized vent, so the remaining appliances must be tested before the job is finished.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Replacement of a boiler on an existing common vent

Common causes of do not common vent: removing an old boiler from a common vent

  • Existing common vent is too large for the remaining appliances after the old boiler is removed
  • Flue gas spillage or CO emissions when the remaining appliances vent poorly

How to fix do not common vent: removing an old boiler from a common vent: step by step

  1. Inspect the existing vent for correct size, horizontal pitch, blockage, leakage, corrosion and other faults.
  2. Close building doors and windows, and doors to other spaces, as far as practical.
  3. Turn on clothes dryers and any appliance not on the common vent.
  4. Turn on exhaust fans such as range hoods and bathroom fans to full speed. Do not run a summer exhaust fan.
  5. Close fireplace dampers.
  6. Seal unused openings in the common vent.
  7. Run each remaining appliance alone, following its lighting instructions, with the thermostat set to call for continuous operation.
  8. After 5 minutes of main burner operation, check for spillage at the draft hood relief opening using a match, candle or smoke.
  9. Return doors, windows, fans, dampers and other gas appliances to their prior condition.
  10. Correct any improper common vent operation so it meets NFPA 54 or CAN/CSA B149.1. If resizing, approach the minimum size from NFPA 54 Chapter 13 or CAN/CSA B149.1.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

Source: SVF Series 1 Boiler Manual, p. 28. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.