Weil-McLain Boiler: Low water protection and external low water cut-off
Low water protection and external low water cut-off on a Weil-McLain boiler: The U-Control uses a dual sensor in the heat exchanger for low water protection. Some jurisdictions require an external low water cut-off.
Applies to: Ultra low water protection
Common causes of low water protection and external low water cut-off
- Difference between the two heat exchanger sensors exceeds 10 °F
How to fix low water protection and external low water cut-off: step by step
- The U-Control compares the two sensor readings and keeps them within 10 °F of each other.
- If the difference is more than 10 °F, the boiler shuts down on automatic reset.
- Where code requires, install an external low water cut-off as shown in the wiring diagrams.
- Where possible, use the Weil-McLain Ultra low water cut-off kit, which has a probe-type cut-off and a plug-in harness.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain Ultra Series 4 boiler manual, p. 95. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.